VERO 1500 VE EC
 |
(1) supply
(2) exhaust |
|
VERO |
1500VE EC |
|
Efficiency/compression |
[m3/h]/[Pa] |
1000/360 |
|
Heater |
- phase/voltage |
[50Hz/VAC] |
~3, 400 |
|
|
- power consumption |
[kW] |
4,5 |
|
Fans |
- phase/voltage |
[50Hz/VAC] |
~1, 230 |
|
- exhaust |
- power/current |
[kW/A] |
0,540/3,38 |
|
|
- fan speed |
[min-1] |
3580 |
|
- supply |
- power/current |
[kW/A] |
0,540/3,38 |
|
|
- fan speed |
[min-1] |
3580 |
|
Motor protection class |
|
IP-44 |
|
Thermal efficiency |
|
74% |
|
Max power consumption |
[kW/A] |
5,07/9,13 |
|
Automatic control |
|
integrated |
|
Filter class - exhaust |
|
EU5 |
|
Filter class - supply |
|
EU5 |
|
Thermal insulation |
[mm] |
50 |
|
Weight |
[kg] |
160,0 |
VERO 1500 VW EC
 |
(1) supply
(2) exhaust |
|
VERO |
1500VW EC |
|
Efficiency/compression |
[m3/h]/[Pa] |
1000/360 |
|
Water heater |
- power |
[kW] |
NVS 315 |
|
|
- water Tin/Tout |
[°C] |
|
|
- water pressure drop |
[kPa] |
|
Fans |
- phase/voltage |
[50Hz/VAC] |
~1, 230 |
|
- exhaust |
- power/current |
[kW/A] |
0,540/3,38 |
|
|
- fan speed |
[min-1] |
3580 |
|
- supply |
- power/current |
[kW/A] |
0,540/3,38 |
|
|
- fan speed |
[min-1] |
3580 |
|
Motor protection class |
|
IP-44 |
|
Thermal efficiency |
|
74% |
|
Max power consumption |
[kW/A] |
1,08/6,83 |
|
Automatic control |
|
integrated |
|
Filter class - exhaust |
|
EU5 |
|
Filter class - supply |
|
EU5 |
|
Thermal insulation |
[mm] |
50 |
|
Weight |
[kg] |
160,0 |
Air flow temperature range from -20°C to +40°C
Designed for operation indoors only.
Thermal efficiency of VERO 1500VE EC was measured at 1500m3/h, at temperature range from -20°C to +20°C.
Thermal efficiency of VERO 1500VW EC was measured at 1500m3/h, at temperature range from -20°C to +20°C.
VERO 1500 HE EC
 |
(1) supply
(2) exhaust |
|
VERO |
1500HE EC |
|
Efficiency/compression |
[m3/h]/[Pa] |
1000/360 |
|
Heater |
- phase/voltage |
[50Hz/VAC] |
~3, 400 |
|
|
- power consumption |
[kW] |
4,5 |
|
Fans |
- phase/voltage |
[50Hz/VAC] |
~1, 230 |
|
- exhaust |
- power/current |
[kW/A] |
0,518/3,25 |
|
|
- fan speed |
[min-1] |
3580 |
|
- supply |
- power/current |
[kW/A] |
0,524/3,30 |
|
|
- fan speed |
[min-1] |
3580 |
|
Motor protection class |
|
IP-54 |
|
Thermal efficiency |
|
74% |
|
Max power consumption |
[kW/A] |
5,56/13,20 |
|
Automatic control |
|
integrated |
|
Filter class - exhaust |
|
EU5 |
|
Filter class - supply |
|
EU5 |
|
Thermal insulation |
[mm] |
50 |
|
Weight |
[kg] |
159,0 |
VERO 1500 HW EC
 |
(1) supply
(2) exhaust |
|
VERO |
1500HW EC |
|
Efficiency/compression |
[m3/h]/[Pa] |
1000/360 |
|
Water heater |
- power |
[kW] |
5,45 |
|
|
- water Tin/Tout |
[°C] |
80/60 |
|
|
- water flow rate |
[l/s] |
0,07 |
|
|
- water pressure drop |
[kPa] |
2,3 |
|
|
- kvs value |
[m3/h] |
1,7 |
|
Fans |
- phase/voltage |
[50Hz/VAC] |
~1, 230 |
|
- exhaust |
- power/current |
[kW/A] |
0,518/3,25 |
|
|
- fan speed |
[min-1] |
3580 |
|
- supply |
- power/current |
[kW/A] |
0,524/3,30 |
|
|
- fan speed |
[min-1] |
3580 |
|
Motor protection class |
|
IP-44 |
|
Thermal efficiency |
|
74% |
|
Max power consumption |
[kW/A] |
1,05/6,63 |
|
Automatic control |
|
integrated |
|
Filter class - exhaust |
|
EU5 |
|
Filter class - supply |
|
EU5 |
|
Thermal insulation |
[mm] |
50 |
|
Weight |
[kg] |
165,0 |
Air flow temperature range from -20°C to +40°C
Designed for operation indoors only.
Thermal efficiency of VERO 1500HE EC was measured at 1500m3/h, at temperature range from -20°C to +20°C.
Thermal efficiency of VERO 1500HW EC was measured at 1500m3/h, at temperature range from -20°C to +20°C.
VERO 1500VE EC, VERO 1500VW EC
 |
|
L |
W |
H |
Ø D |
H1 |
F |
|
853 mm |
1300 mm |
1150 mm |
315 mm |
70 mm |
40 mm |
|
VERO 1500HE EC, VERO 1500HW EC
 |
|
L |
W |
H |
Ø D |
H1 |
F |
|
1350 mm |
853 mm |
900 mm |
315 mm |
70 mm |
40 mm |
|
VERO 1500VE EC
A - fresh air
B - supply air
C - extract air
D - exhaust air |
|
IV - exhaust air fan
PV - supplied air fan
RR - rotary heat exchanger
R - rotor motor
KE - electrical heater
PF - fresh air filter (class EU5)
IF - extract air filter (class EU5)
TJ - air temperature sensor
TL - air temperature sensor |
VERO 1500VW EC
A - fresh air
B - supply air
C - extract air
D - exhaust air |
|
NVS - optionally supplied water heater
IV - exhaust air fan
PV - supplied air fan
RR - rotary heat exchanger
R - rotor motor
PF - fresh air filter (class EU5)
IF - extract air filter (class EU5)
TJ - air temperature sensor
TL - air temperature sensor
M1 - optionally supplied mixing valve and motor |
VERO 1500HE EC
A - fresh air
B - supply air
C - extract air
D - exhaust air |
|
IV - exhaust air fan
PV - supplied air fan
RR - rotary heat exchanger
R - rotor motor
KE - electrical heater
PF - fresh air filter (class EU5)
IF - extract air filter (class EU5)
TJ - air temperature sensor
TL - air temperature sensor |
VERO 1500HW EC
A - fresh air
B - supply air
C - extract air
D - exhaust air |
|
IV - exhaust air fan
PV - supplied air fan
RR - rotary heat exchanger
R - rotor motor
KV - water heater
PF - fresh air filter (class EU5)
IF - extract air filter (class EU5)
TJ - air temperature sensor
TL - air temperature sensor
T1 - air temperature sensor
T2 - surface temperature sensor
M1 - optionally supplied mixing valve and motor |
|
|
 |
|
 |
|
|