VERO 4000 HE
 |
(1) supply
(2) exhaust |
|
VERO |
4000HE |
|
Efficiency/compression |
[m3/h]/[Pa] |
4000/610 |
|
Heater |
- phase/voltage |
[50Hz/VAC] |
~3, 400 |
|
|
- power consumption |
[kW] |
18,0 (9+9) |
|
Fans |
- phase/voltage |
[50Hz/VAC] |
~3, 400 |
|
- exhaust |
- power/current |
[kW/A] |
3,7/6,0 |
|
|
- fan speed |
[min-1] |
1320 |
|
- supply |
- power/current |
[kW/A] |
3,7/6,0 |
|
|
- fan speed |
[min-1] |
1320 |
|
Motor protection class |
|
IP-54 |
|
Thermal efficiency |
|
71% |
|
Max power consumption |
[kW/A] |
25,5/38,3 |
|
Automatic control |
|
opcja |
|
Filter class - exhaust |
|
EU5 |
|
Filter class - supply |
|
EU5 |
|
Thermal insulation |
[mm] |
50 |
|
Weight |
[kg] |
490,0 |
VERO 4000 HW
 |
(1) supply
(2) exhaust |
|
VERO |
4000HW |
|
Efficiency/compression |
[m3/h]/[Pa] |
4000/510 |
|
Water heater |
- power |
[kW] |
16,29 |
|
|
- water Tin/Tout |
[°C] |
80/60 |
|
|
- water flow rate |
[l/s] |
0,20 |
|
|
- water pressure drop |
[kPa] |
2,1 |
|
|
- kvs value |
[m3/h] |
11,85 |
|
Fans |
- phase/voltage |
[50Hz/VAC] |
~3, 400 |
|
- exhaust |
- power/current |
[kW/A] |
3,7/6,0 |
|
|
- fan speed |
[min-1] |
1320 |
|
- supply |
- power/current |
[kW/A] |
3,7/6,0 |
|
|
- fan speed |
[min-1] |
1320 |
|
Motor protection class |
|
IP-54 |
|
Thermal efficiency |
|
71% |
|
Max power consumption |
[kW/A] |
7,5/12,3 |
|
Automatic control |
|
opcja |
|
Filter class - exhaust |
|
EU5 |
|
Filter class - supply |
|
EU5 |
|
Thermal insulation |
[mm] |
50 |
|
Weight |
[kg] |
490,0 |
Air flow temperature range from -20°C to +40°C
Designed for operation indoors only.
Thermal efficiency of VERO 4000HE was measured at 4000m3/h, at temperature range from -20°C to +20°C.
Thermal efficiency of VERO 4000HW was measured at 4000m3/h, at temperature range from -20°C to +20°C.
VERO 4000HE, VERO 4000HW
 |
|
L |
W |
H |
D |
d |
H1 |
F |
|
2100 mm |
1205 mm |
1200 mm |
800 mm |
500 mm |
120 mm |
65 mm |
|
VERO 4000HE
A - fresh air
B - supply air
C - extract air
D - exhaust air
* - supplied with integrated automatic
controll (VERO 400HE-1500HE). |
|
IV - exhaust air fan
PV - supplied air fan
RR - rotary heat exchanger
R - rotor motor
KE - electrical heater
PF - fresh air filter (class EU5)
IF - extract air filter (class EU5)
TJ - air temperature sensor *
TL - air temperature sensor * |
VERO 4000HW
A - fresh air
B - supply air
C - extract air
D - exhaust air
* - supplied with integrated automatic
controll (VERO 1500HW). |
|
IV - exhaust air fan
PV - supplied air fan
RR - rotary heat exchanger
R - rotor motor
KV - water heater
PF - fresh air filter (class EU5)
IF - extract air filter (class EU5)
TJ - air temperature sensor *
TL - air temperature sensor *
T1 - air temperature sensor *
T2 - surface temperature sensor*
M1 - optionally supplied mixing valve and motor |
|
|
 |
|
 |
|
|