VEKU 3000 HE
 |
(1) supply
(2) exhaust |
|
VEKU |
3000HE |
|
Efficiency/compression |
[m3/h]/[Pa] |
3000/360 |
|
Heater |
- phase/voltage |
[50Hz/VAC] |
~3, 400 |
|
|
- power consumption |
[kW] |
24,0 (9+15) |
|
Pre-heater for heat exchanger |
[kW] |
- |
|
Fans |
- phase/voltage |
[50Hz/VAC] |
~3, 400 |
|
- exhaust |
- power/current |
[kW/A] |
2,5/4,1 |
|
|
- fan speed |
[min-1] |
1300 |
|
- supply |
- power/current |
[kW/A] |
2,5/4,1 |
|
|
- fan speed |
[min-1] |
1300 |
|
Motor protection class |
|
IP-54 |
|
Thermal efficiency |
|
59% |
|
Maks. power consumption |
[kW/A] |
29,0/44,7 |
|
Automatic control |
|
opcja |
|
Filter class - exhaust |
|
EU5 |
|
Filter class - supply |
|
EU5 |
|
Thermal insulation |
[mm] |
50 |
|
Weight |
[kg] |
395,0 |
VEKU 3000 HW
 |
(1) supply
(2) exhaust |
|
VEKU |
3000HW |
|
Efficiency/compression |
[m3/h]/[Pa] |
3000/260 |
|
Water heater |
- power |
[kW] |
20,2 |
|
|
- water Tin/Tout |
[°C] |
80/60 |
|
|
- water flow rate |
[l/s] |
0,25 |
|
|
- water pressure drop |
[kPa] |
10,3 |
|
|
- kvs value |
[m3/h] |
2,8 |
|
Pre-heater for heat exchanger |
[kW] |
- |
|
Fans |
- phase/voltage |
[50Hz/VAC] |
~3, 400 |
|
- exhaust |
- power/current |
[kW/A] |
2,5/4,1 |
|
|
- fan speed |
[min-1] |
1300 |
|
- supply |
- power/current |
[kW/A] |
2,5/4,1 |
|
|
- fan speed |
[min-1] |
1300 |
|
Motor protection class |
|
IP-54 |
|
Thermal efficiency |
|
59% |
|
Maks. power consumption |
[kW/A] |
5,0/8,2 |
|
Automatic control |
|
opcja |
|
Filter class - exhaust |
|
EU5 |
|
Filter class - supply |
|
EU5 |
|
Thermal insulation |
[mm] |
50 |
|
Weight |
[kg] |
395,0 |
Air flow temperature range from -20°C to +40°C
Designed for operation indoors only.
Thermal efficiency of VEKU 3000HE was measured at 1900m3/h, at temperature range from -20°C to +20°C.
Thermal efficiency of VEKU 3000HW was measured at 1900m3/h, at temperature range from -20°C to +20°C.
VEKU 3000HE, VEKU 3000HW
 |
|
L |
W |
H |
Ø D |
H1 |
F |
|
2400 mm |
830 mm |
1130 mm |
400 mm |
120 mm |
65 mm |
|
VEKU 3000HE
A - fresh air
B - supply air
C - extract air
D - exhaust air |
|
IV - exhaust air fan
PV - supply air fan
PR - plate heat exchanger
KE - electrical heater
PF - filter for supply air (class EU5)
IF - filter for extract air (class EU5)
M - by-pass damper |
VEKU 3000HW
A - fresh air
B - supply air
C - extract air
D - exhaust air |
|
IV - exhaust air fan
PV - supply air fan
PR - plate heat exchanger
KV - water heater
PF - filter for supply air (class EU5)
IF - filter for extract air (class EU5)
M - by-pass damper
M1 - optionally supplied mixing valve and motor |
|
|
 |
|
 |
|
|