The Thermozone AC/WAC400 range consists of both heated and ambient versions and hot water heated WAC models. AC/WAC400 are designed for permanent horizontal installation above doorways with heights between 3,0 and 4,0 meters or positioned vertically beside the doorway when over door space is limited. They can be surface mounted or recessed into a false ceiling. A jet of air from the air curtain prevents cold draughts through open doorways and increases comfort levels in the proximity of the door.
Characteristics:
- corrosion proof houing made of hot zinc-plated and powder enamelled steel panels; color: RAL 9016
- compact design for installation where space is limited
- adjustable mounting brackets for optimal air stream
- the connection areas are easily accessed through a large service hatch
- the sound-absorbing front plate can be turned to allow air intake either from above or from below
- the narrow outlet which gives a high impulse, is angled 10° outwards for optimal performance
| Cold curtains |
| Parameters |
AC 401 |
AC 402 |
| Power |
[kW] |
0,6 |
1,0 |
| Motor voltage |
[V] |
230~ |
230~ |
| Motor amperage |
[A] |
2,6 |
4,3 |
| Airflow |
[m³/h] |
1350/2700 |
2250/4500 |
| Noise level* |
[dB(A)] |
44/62 |
45/63 |
| Weigth |
[kg] |
44 |
71 |
| Dimensions (L×D×H) |
[mm] |
1000×710×400 |
1665×710×400 |
| Protection class |
|
IP 24 |
IP 24 |
| Electrical curtains |
| Parameters |
AC 412 |
AC 418 |
| Power |
[kW] |
12 |
18 |
| Motor voltage |
[V] |
230~ |
230~ |
| Motor amperage |
[A] |
2,6 |
4,3 |
| Heater voltage |
[V] |
400 V3~ |
400 V3~ |
| Heater aperage |
[A] |
13,1 |
19,7 |
| Airflow |
[m³/h] |
1350/2700 |
2250/4500 |
| Noise level* |
[dB(A)] |
44/62 |
45/63 |
| Weigth |
[kg] |
54 |
86 |
| Dimensions (L×D×H) |
[mm] |
1000 x 710 x 400 |
1665 x 710 x 400 |
| Protection class |
|
IP 24 |
IP 24 |
| Air temperature incr.** |
[°C] |
27/13 |
27/13 |
| Water curtains |
| Parameters |
Montaż poziomy |
Montaż pionowy |
| WAC 401 |
WAC 402 |
WAC 401V |
WAC 402V |
| Motor voltage |
[V] |
230~ |
230~ |
230~ |
230~ |
| Motor amperage |
[A] |
2,5 |
4,2 |
2,5 |
4,2 |
| Airflow |
[m³/h] |
1050/2400 |
1800/4000 |
1050/2400 |
1800/4000 |
| Liquid capacity |
[l] |
2,5 |
3,5 |
2,5 |
3,5 |
| Flow resistance |
[kPa] |
1,1/7,8 |
0,6/4,4 |
1,1/7,8 |
0,6/4,4 |
| Noise level* |
[dB(A)] |
44/62 |
45/63 |
44/62 |
45/63 |
| Weigth |
[kg] |
52 |
83 |
52 |
83 |
| Dimensions (L×D×H) |
[mm] |
1000×710×400 |
1665×710×400 |
1000×710×400 |
1665×710×400 |
| Protection class |
|
IP 44 |
IP 44 |
IP 44 |
IP 44 |
* distance from the source 5m, direction coefficient, absorption surface 200m²
** Air temperature incr. Δt mierzony przy całkowitej Power y grzewczej i średnich/najwyższych obrotach wentylatora.
|
|
 |
|
 |
|
|